Engineering tools
Power and energy calculators
Pick a calculator. Results update as you type.
Solar system sizing
List what you want to power and for how long each day.
1What will it power?
2Site and equipment
Peak sun hours are typically 3 to 6 a day, depending on location and season. Backup days are how long the battery must last with no sun.
Adjust assumptions
How this is calculated
- Array size = daily energy ÷ inverter efficiency ÷ (peak sun hours × panel output after losses).
- Battery size = daily energy ÷ inverter efficiency × backup days ÷ usable fraction.
- The inverter figure assumes every appliance runs at once, plus headroom. Motors and compressors need extra surge capacity.
- The charge controller figure includes a 25% margin.
- Daily energy use
- 3.3 kWh
- Peak load
- 470 Weverything on at once
- Solar array
- 1,200 W978 W needed
- Battery bank
- 191 Ahat 24 V
- Inverter
- 588 W or larger
- Charge controller
- 63 A or larger
A first estimate for planning. Have a qualified engineer check the final design.
Cable size and voltage drop
Find the smallest standard cable that keeps voltage drop within your limit.
How this is calculated
- This sizes for voltage drop only. The cable must also carry the current safely for its installation method, grouping and ambient temperature, and suit the protective device.
- Drop = 2 × resistivity × length × current ÷ area for DC and single-phase, with √3 in place of 2 for three-phase.
- Resistivity in service: 0.0225 Ω·mm²/m for copper and 0.036 Ω·mm²/m for aluminium. Cable reactance is ignored, which matters for large cables.
- Voltage drop
- 1.88%4.32 V of 230 V
- Calculated minimum
- 6.26 mm²
Voltage drop only. Also check the cable can carry the current safely.
A first estimate for planning. Have a qualified engineer check the final design.
Battery runtime
See how long a battery bank will carry a steady load.
Inverter is its efficiency. Use 100 for a DC load with no inverter.
How this is calculated
- Runtime = voltage × capacity × usable fraction × inverter efficiency ÷ load.
- Real runtime is shorter at high discharge rates, in cold conditions and as the battery ages.
- Usable energy
- 3.46 kWh
- Stored energy
- 4.8 kWh
A first estimate for planning. Have a qualified engineer check the final design.
Generator sizing
Find the generator rating that runs your loads and starts the largest motor.
Running load is everything on together, motors included. Enter 0 for the motor if there are none.
Adjust assumptions
How this is calculated
- The rating is the larger of running demand ÷ maximum loading, and demand while the largest motor starts.
- A starting multiplier of 3 is common for direct-on-line starting. Soft starters and variable speed drives reduce it; check the motor data.
- Site altitude and temperature reduce generator output. Apply the manufacturer's derating.
- Running demand
- 10 kVA
- At 80% loading
- 12.5 kVA
- While the motor starts
- 15 kVA
A first estimate for planning. Have a qualified engineer check the final design.