Engineering tools

Power and energy calculators

Pick a calculator. Results update as you type.

Cable size and voltage drop

Find the smallest standard cable that keeps voltage drop within your limit.

V
A
m
%
How this is calculated
  • This sizes for voltage drop only. The cable must also carry the current safely for its installation method, grouping and ambient temperature, and suit the protective device.
  • Drop = 2 × resistivity × length × current ÷ area for DC and single-phase, with √3 in place of 2 for three-phase.
  • Resistivity in service: 0.0225 Ω·mm²/m for copper and 0.036 Ω·mm²/m for aluminium. Cable reactance is ignored, which matters for large cables.
Use at least
10 mm²
copper conductor, for voltage drop
Voltage drop
1.88%4.32 V of 230 V
Calculated minimum
6.26 mm²

Voltage drop only. Also check the cable can carry the current safely.

A first estimate for planning. Have a qualified engineer check the final design.